VWG-40
Viconics Wireless Gateway
Hardware Installation Guide
(Issue Date September 24, 2008 – 028-0179 R8)
Product overview
The VWG-40 and related wireless thermostats are targeted to retrofit applications where the
addition of communicating field bus wiring within the building space is prohibitive. The
Gateway and Communicating Thermostats with wireless field bus encourages the use of
existing wiring utilized by existing electronic thermostat type controls.
The VWG-40 when utilized in conjunction with the VT7xxxXxxxxW series wireless thermostats will offer the integrator
simple BACnet IP or BACnet MS/TP objects to integrate over standard building automation systems using familiar
integration toolsets.
A maximum of 30 wireless thermostats can be wirelessly attached to a single VWG
The following additional documentation is available on www.viconics.com
Gateway BACnet integration guide (VWG-40-IP & VWG-40-MSTP), is available in document ITG-VWG-40-BAC-Exx
Information on design consideration of wireless mesh networks and VWG set-up / diagnostics is available in document LIT-
VWG-40-SETUP-Exx
Part available
Part number Description
VWG-40-IP-1000 Viconics BACnet over IP wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-40-MSTP-1000 Viconics BACnet RS485 MS-TP wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-40-LON-1000
(Upcoming)
Viconics LON wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-APP
Interface software for VWG configuration and set-up. Operates under Windows XP .
Uses a LAN crossover IP connection for initial set-up.
VWG-RA
Remote antenna for gateway when the gateway is installed inside a metal cabinet or
when remote antennal mounting is required by physical installation
VWG-WA Replacement antenna for gateway mounted antenna setup
VWG-PS-DC 24 Vac to 15 Vdc panel mounted power supply for VWG
VWG-PS-AC 120 Vac to 15 Vdc power supply for VWG with cord
VWG-BB Replacement battery backup pack for the VWG
Trademarks
Niagara, Niagara AX is a registered trademark of Tridium, Inc.
LON, LonWorks and LonTalk are registered trademarks of Echelon Corporation
BACnet is a registered trademark of ASHRAE
Vedere la pagina 0
1 2 3 4 5 6 ... 12 13

Sommario

Pagina 1 - Hardware Installation Guide

1VWG-40 Viconics Wireless Gateway Hardware Installation Guide (Issue Date September 24, 2008 – 028-0179 R8) Product overview The VWG-40 and rel

Pagina 2

10 2) Apply Power Apply power to the VWG by plugging in the power plug into either the VWG (if wall mount AC adapter VWG-PS-AC) or the 24Vac-powered

Pagina 3

11Using Status LEDs The VWG controller includes several LEDs that can help determine the status of the unit. They are loca

Pagina 4

12 2) Required Battery Maintenance Battery life expectancy is a function of its discharge cycles (the number of discharges and their depth) and the

Pagina 5

13 Canadian Department of Communications( ICES-003) This digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Re

Pagina 6

2 Disclaimers NO WARRANTY. Viconics, Inc. ( herein after referred to as “Viconics” ) makes no warranty as to the accurac

Pagina 7

3 Overview This document covers the mounting and wiring of the Viconics VWG-40 series product. It assumes that you are an

Pagina 8

4 Material and Tools Required The following tools and supplies may be required for installation: • DIN rail, type NS35/7.5 (35mm x 7.5mm), recomm

Pagina 9

5 Mounting Mount the VWG in a location that allows clearance for wiring, servicing, and antenna removal. Environmental R

Pagina 10 - VWG-40-SETUP-Exx

6 Removing and Replacing the Cover You must remove the VWG cover to connect the battery (new unit) or to replace the battery. The cover snaps onto

Pagina 11

7Board Layout Figure below shows the location of LEDs, connections and other features of the VWG with the cover removed. Wirin

Pagina 12 - • Fuse

8VWG-PS-AC 120 Vac Wall mounted power supply module Both the U.S. and International models of wall power modules are self-contained

Pagina 13

9RS485—BACnet MS-TP wiring. An RS485, optically isolated port uses a 3-position, screw terminal connector and always operates as COM2. Wire to th