setpoint devices
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
APPLICATIONS
Hospitals and operating rooms, pharmaceutical labs
Clean rooms
Food processing plants
Environmental testing facilities, and other institutional applications
FEATURES
Independent RH and T (HT relay) or analog setpoint outputs (HT analog)
provide application exibility
LCD for local display of readings and setup values
Oset function adjusts calibration intervals for both RH and T (HT models)
Switch-selectable 4-20mA or 0-10V/0-5VDC analog outputs
Multi-point calibration to 1% RH, traceable to NIST
Replaceable RH sensor element supports eld calibration oset...saves time
Semiconductor temperature sensor can be eld calibrated
Independent RH, Temp, and
Analog Setpoint Outputs
Wall Mount Humidity
Transmier Thermostat
Humidistat Functions
DESCRIPTION
All HT/HWS Series institutional grade relative humidity/temperature transmitters
are designed to meet the rigorous needs of pharmaceutical labs, hospitals, science
labs, and other settings that call for precise environmental control. Internal jumpers
control access to a feature that allows adjustment of the calibration osets. The
devices can also be made tamper resistant using a jumper to disable keypad
programing functions. HT/HWS models are calibrated with NIST traceable
calibration equipment.
Analog Output Transmitter
Analog output models feature a keypad to make adjusting humidity and
temperature setpoint values easy. They transmit the setpoint values back to a control
system by means of dual outputs. A slide-switch allows easy selection of output
type, either 4-20mA or 0-5V/0-10VDC signals. Dual outputs enable eortless control
of both humidity and temperature in a single, compact sensor.
Setpoint Relay Transmitter
The HT Series setpoint relay models also oer thermostat or humidistat functionality.
Two separate relays can be congured to control heating and cooling when in
thermostat mode, or humidifying and de-humidifying when in humidistat mode.
HWS models oer the same precise humidity measurement and control as the HT,
but without the temperature and thermostat features.
SPECIFICATIONS
Input Power 15 to 30VDC/24VAC, 100mA max.
Outputs, Analog Switch-selectable 4-20mA, or 0-10V/0-5VDC (switch aects both outputs)
Outputs, Relay (Relay models only) 2 Form C (SPDT), 1A 30VDC, resistive, 30W max.
HS Element Digitally proled thin-lm capacitive (32-bit mathematics) U.S. Patent 5,844,138†
Accuracy at 25°C from 10-80% RH* (Multi-point calibration NIST traceable) ±2%, 3%, or 5% models ; ±1% at 20-50% RH on HTA models
±1% at 12-40% RH on HTR models in mA output mode; ±1% at 30% RH on HTR models in voltage output mode
Reset Rate** 24 hours
Stability ±1% @ 20°C (68°F) annually, for two years
Hysteresis RH: 1.5% (typical), Temp: 1° to 10°F in 1°F increments
Linearity Included in accuracy spec.
Operating Humidity Range 0-100% RH non-condensing
Temperature Coecient ± 0.1%RH/°C above or below 25°C (typical)
Operating Temperature Range 10° to 35°C (50° to 95°F)
Temperature Accuracy ±1.0°C1.8°F)
Scaling RH: 0-100%; Temp: 10°to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F) menu selectable
Calibration Oset RH: Adjustable ±10% in 0.1% increments; Temp: Adjustable ±10° in 0.1° increments
Setpoint Range RH: 10-80% in 1% increments; Temp: minimum to full scale in 1°F increments
† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.
* Specied accuracy with 24VDC supplied power with rising humidity
**Reset Rate is time required to recover to 50% RH after exposure to 90% RH for 24 hours
One side of transformer secondary is connected to signal common, so an isolation transformer or dedicated power supply may be required.
RTD/Thermistors in wall packages are not compensated for internal heating of product.
HT
HT/HWS SERIES
HQ0001872.B 01131
Vedere la pagina 0
1 2

Sommario

Pagina 1 - Humidistat Functions

setpoint devicesVERIS INDUSTRIES800.354.8556+1 503.598.4564www.veris.comAPPLICATIONS● Hospitals and operating rooms, pharmaceutical labs ● Clean roo

Pagina 2 - ORDERING INFORMATION

setpoint devices800.354.8556+1 503.598.4564www.veris.comDIMENSIONAL DRAWINGAPPLICATION/WIRING DIAGRAMSCONFIGURATIONSetpointAccuracyNISTA = AnalogR = R

Commenti su questo manuale

Nessun commento