current monitoring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
Status And Control In One Package
Current Switches with Relay:
Adjustable Trip Point, High
Voltage Output
DESCRIPTION
Hawkeye Relay Combination Series high voltage output current switches are the
ideal solution for the automation installer. These units combine a current switch
and relay into a single package, reducing the space required for total control of fans
and pumps. The integrated current switch and relay operate independently of one
another. All relay connections are externally available for maximum exibility.
These products perform the functions of start/stop and status monitoring with one
device instead of two.
APPLICATIONS
Starting/stopping and monitoring positive status of motors
Detecting belt loss and coupling shear
FEATURES
Combines command relay & fan/pump status sensor in a single, easy to
install unit
Reduces number of components installed...ts better in small starter enclosures
Command relay and status in a single unit
Easier to install than dierential pressure switches...no additional wiring
needed
Detect belt loss and motor failure...ideal for fan and pump status
Bracket on H939, H949, and H959 can be installed in three dierent
congurations...added exibility
H749 and H949 feature SPDT command relay...saves installation time
Reduced charges from electrician
Relay and status LEDs for easy setup
Polarity insensitive status output...fast trouble-free installation
Adjustable trip point for current sensor status...ts many applications
5-year warranty
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power Induced from monitored conductor
Insulation Class 600VAC RMS
Frequency Range 50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% Typical
Terminal Block Wire Size 24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals UL 508 open device listing
Do not use the LED status indicators as evidence of applied voltage.
Year
Warranty
5
Voltage AC DC
24V................................... 10mA 10mA
12V.................................................................... 20mA
TYPICAL COIL PERFORMANCE
Hx39, Hx59 (SPST, N.O.)
Resistive................................. 10A@250VAC, 30VDC
Inductive................................ 5A@250VAC, 30VDC
Hx49 (SPDT)
Resistive.............................. 8A@250VAC, 30VDC
Inductive............................. 3.5A@250VAC, 30VDC
RELAY CONTACT RATINGS
Pull In Voltage
Hx39 .............................................................. 20.1VDC
Hx49 .............................................................. 20.1VDC
Hx59 .............................................................. 8.4VDC
Drop Out Voltage
Hx39 .............................................................. 5.2VDC
Hx49 .............................................................. 5.2VDC
Hx59 .............................................................. 3.0VDC
H739
H939
H739 SERIES & H939 SERIES
TM
DETECTS BELT LOSS/COUPLING SHEAR!
DETECTS BELT LOSS/COUPLING SHEAR!
Now you can easily detect when drive belts slip, break, or pump couplings shear.
In fact, a typical HVAC motor that loses its load has a reduction of current draw
of up to 50%. That’s why our sensors are the industry standard for status.
Calibrated
Trip Point
O O
Fan/pump
On
Loss of Belt/Coupling Shear
Electrical
Failure
HQ0001761.C 01131