H704-42(H)(E), H704-42/1(H)(E)
General:
Operating Temp. Range 0° to 60°C (32° to 140°F) (<95% RH, non-condensing)
Storage Temp. Range -40° to 70°C (-40° to 158°F)
Control (Mains) Power Source 120 VAC L-N, 50/60 Hz (208/230 VAC for H704-42/1(E))
(+10/-25%) Input current < 75 mA
Primary Fusing 250 VAC/100 mA, (T) 5 x 20 mm, (if equipped) Littelfuse 218 series
or equivalent
Altitude of Operation 3 km max.
Measured Current Inputs:
Number of Channels 42
Frequency 50/60 Hz
Sample Frequency 1280 Hz
Update Rate 1.2 sec
Accuracy ±2% from 5 A to 50 A *
Overload Capability Tested to 10,000 A single-cycle
Connection to Conductor Solid-core toroid
Measured Currents Current range 0-50 A (max. conductor size is AWG#6 THHN)
Measured Currents, H version Current range 0-100 A (max. conductor size is AWG#2 THHN)
Network Communications:
Type Modbus RTU
Connection DIP switch-selectable 2-wire or 4-wire
Address DIP switch-selectable address 1 to 247
Baud Rate DIP switch-selectable 2400, 4800, 9600, 19200
Parity DIP switch-selectable NONE, ODD, EVEN
Communication Format 8-data-bits, 1-start-bit, 1-stop-bit
Termination 5-position depluggable connector
(TX+ TX- SHIELD TX+/RX+ TX-/RX-)
Defaults:
Warning Register 60% of current sensor max. (configurable)
Alarm Register 70% of current sensor max. (configurable)
Breaker Size Register 20 A
* In case of a current fault above 60A (120 for the H version), all adjacent channels will report
higher than actual readings. To prevent this from causing over-current warnings and alarms,
configure the warning and alarm delays for a longer time period than the response time of the
breaker.
quick install
Installer's Specifications
1. Disconnect and lock out power.
2. Mount current sensor strips adjacent to breaker terminations.
3. Verify that serial numbers on CT and board match.
4. Mount board onto electrical/fire enclosure.
5. Connect CTs and wire the board.
6. Reconnect power.
7. Configure communication and addressing parameters.
Note: Data acquisition board and CT strips are calibrated as a set. Match the serial
numbered parts together.
MODEL # CT SPACING
H704-42(H)(E) ¾" on center
H704-42/1(H)(E) 1" on center
For a 400A Panel, order the H704-42Y55
Branch Current Monitor